Emergency and Exit Lighting Maintenance – Why It Matters and How We Deliver It

September 6, 2026

Emergency and exit lighting is one of those systems you hope you never need - but when you do, it must perform without hesitation. In a power outage, fire event, or emergency evacuation, these systems are critical to guiding occupants safely from a building.

At BOSCHETTI, we maintain emergency and exit lighting systems in accordance with AS/NZS 2293.2, ensuring compliance, reliability and peace of mind for building owners and facility managers.

Below is an overview of our structured maintenance approach.

Built on Compliance and Proven Methodology

Our maintenance procedure is aligned with Australian and New Zealand standards and is designed to ensure:

  • Systems remain in a constant state of readiness
  • Performance meets required emergency duration times
  • Faults are identified and rectified promptly
  • Accurate records are maintained in the site logbook

We follow a disciplined, repeatable process - not a “tick-and-flick” inspection.

Six-Monthly Maintenance

At intervals not exceeding six months, we carry out functional testing of emergency luminaires and exit signs.

This includes:

  • Simulating mains power failure to initiate battery operation
  • Confirming luminaires and exit signs operate correctly on battery supply
  • Verifying the system sustains illumination for the required in-service duration
  • Ensuring all fittings are returned to normal operation after testing
  • Recording results and any corrective actions in the site logbook

Where fittings fail to operate satisfactorily, we repair or replace them promptly, including battery replacement where required.

For larger installations, we may use a rotational testing methodology - ensuring no individual fitting exceeds the prescribed maintenance interval.

Twelve-Monthly Maintenance

Annually, we undertake a more comprehensive inspection, which includes:

  • All six-monthly functional checks
  • Cleaning of light-emitting and reflective surfaces
  • Visual confirmation that emergency lighting operates correctly in relation to the normal lighting system
  • Verification of system performance under discharge testing

This ensures not only operational compliance, but also that illumination levels are not compromised by environmental factors such as dust accumulation or degradation of components.

Duration of Operation - What We Verify

Emergency lighting is not just about switching on - it must remain operational for the required duration.

  • At commissioning, systems are tested beyond the minimum duration to account for future battery degradation
  • During service life, each luminaire and exit sign must operate for at least 90 minutes on emergency power (unless building regulations specify otherwise)

Our testing methodology verifies this performance while protecting battery integrity and system lifespan.

Record Keeping and Accountability

Every maintenance visit is documented in the site logbook, including:

  • Test outcomes
  • Any faults identified
  • Corrective actions taken
  • Component replacements

This provides an auditable compliance trail and protects building owners in the event of regulatory inspection or incident investigation.

Confidence Through Competence

Emergency lighting maintenance is not simply about pressing a test button. It requires:

  • Understanding of compliance obligations
  • Knowledge of battery behaviour and lifecycle management
  • Correct discharge testing techniques
  • Awareness of system design intent

At BOSCHETTI, we approach emergency lighting as electrical professionals - not just maintenance contractors. Our procedures are structured, standards-based, and designed to ensure your system performs when it matters most.